The HCYK-1D is a 4.5kW CO2 heat pump suitable for new and existing heating installations. This CO2 heat pump functions in the same way as a heat pump with conventional refrigerants. By using CO2 as a refrigerant, the heat pump can operate much more efficiently in a high temperature range and performs more efficiently at low ambient temperatures. Due to the maximum outlet temperature of 90°C, the CO2 heat pumps can be used for the production of domestic hot water.
When the heating installation combined with the buffer tanks is adjusted correctly, the CO2 heat pumps can used to completely replace existing gas boilers for space heating. Existing central heating installations often require a minimum supply temperature of 80°C. The CO2 heat pumps are therefore an excellent device to make existing buildings more sustainable. The CO2 heat pumps are suitable for collective heating in apartment buildings, small district heating systems, sanitary hot water production for swimming pools, sports accommodations, hotels and holiday parks. By combining the central heating system with hot water production, the Seasonal Performance Factor (SPF) becomes even better.
Model | HCYK-1D |
---|---|
Power supply | 1Ph/230V/50Hz + N + E |
Max outlet temperature | 90°C |
Rated current | 6.7 A |
Maximum starting current | 13.5 A |
Maximum power input | 2600 W |
Refrigerant code | R744 |
Refrigerant charge | 1.2 kg |
Noise level | ≤ 41 dB(A) |
pressure drop gas cooler | ± 40-45 kPa |
Water side connections | 2 x ¾" |
Applicable ambient temperature | -25~+43 ℃ |
Weight | 88 kg |
Test conditions: | Nominal | Standard | Low |
---|---|---|---|
Ambient temperature | DB/WB: 7/6°C | DB/WB: 20/19°C | DB/WB: -7/-6°C |
Inlet temperature | 30°C | 30°C | 30°C |
Outlet temperature: | 80°C | 80°C | 80°C |
Heating power | 4463W | 4463W | 4463W |
Power input | 1889W | 1889W | 1889W |
COP | 2.36 | 2.90 | 1.89 |
Water flow: | 0.07 m³/h | 0.07 m³/h | 0.07 m³/h |